PNPSCADA Web Service Documentation - Events

Events


Event Category: Change Time
(Time) (2)
  Internally generated
EventShortEvent IDTimespaninvalidate?
Change SeasonSeason 9 NY
Change TimeHH:MM 8 YN
DST season changeDsc 740 NN
Error Time base00:00 35 NY
Error Time/date invalidHH:Ms 34 NY
Time/date newly set (old val)old time 33 NY
Time SyncSync 14 YY
  Externally generated
EventShortEvent IDTimespaninvalidate?
Catastrophic Date (Software)!YMD (S) 783 NY
DSTDST 717 NN
DST changeDSTchange 759 YN
Error Time/date (Software)HHLMm (S) 656 NN
Time Sync (Software)Sync (S) 657 NN

Event Category: Check Metering
(check) (15)
  Externally generated
EventShortEvent IDTimespaninvalidate?
Presence 0: Small data gapp0 800 YN
Presence 1: Big data gapp1 801 YN
Presence 2: Good check datap2 802 YN
Presence 3: Small zero gapp3 803 YN
Presence 4: Big zero gapp4 804 YN
Presence 5: Inconsistentp5 805 YN
Quality 0: Uncalculatedq0 810 YN
Quality 1: Goodq1 811 YN
Quality 2: Mediumq2 812 YN
Quality 3: Badq3 813 YN
Quality 4: Interventionq4 814 YN
Quality 5: Without attributeq5 815 YN

Event Category: Communication
(Comms) (1)
  Internally generated
EventShortEvent IDTimespaninvalidate?
Alarm register clearedareg=0 788 NN
Cleared Counterscounters-- 775 NN
Cleared Eventsevents-- 60 NY
Cleared Totals DataTotals 17 NY
Clear Energy DataClear 5 NY
Comm. Activity ModificationModify 15 NY
Communication blockedBlocked 29 NN
Communication Downcomms 137 YN
Communication Stopcomms. 825 NN
Control Inputs Status ChangedControl In 18 NY
DCU discovered meterdisc 823 NN
Error Access measuring systemmemory 20 NY
Error during self-testself-test 19 NY
Error register clearedereg=0 787 NN
Error with communication unitComm Unit 21 NN
Error with display & control pDisplay 23 NY
Error with ripple control receRipple 22 NY
Failure of an SMS message tranSMS 31 NY
GAP detection retrygap retry 107 YN
Important operating message reOS msg 32 NY
Init MeterInit 3 YY
Load ProgramLoad 4 NY
Measuring system failedMeasuring 25 NY
Meter programmed incorrectlyprog! 785 NY
Module Communications Sessionmod comm 106 NN
Optical Communications Sessionopt comm 105 NY
Overflow in measuring systemOverflow 24 NY
Processor Resetproc 784 NY
Reprogramming failedReprogram? 26 NY
Restore Energy Datarestore 125 NN
Setting mode failedMode? 27 NY
System failedSystem? 28 NY
UnProgramUnprogram 7 NY
Update ProgramUpdate 6 YY
Wrong flash memory/function exID 30 NY
  Externally generated
EventShortEvent IDTimespaninvalidate?
COM module inserted badCmib 753 NN
COM module inserted okCmio 754 NN
COM module outCmo 755 NN
Function DisconnectFD 735 NN
GPS communicationGPS 743 YN
GSM network failureGnf 747 NN
IO module inserted badImib 756 NN
IO module inserted okImio 757 NN
IO module outImo 758 NN
No connection timeoutNct 729 NN
Remote Ready To ConnectRRTC 734 NN
User ConnectUC 737 NN
User DisconnectUD 736 NN

Event Category: Contactor
(Contact) (13)
  Internally generated
EventShortEvent IDTimespaninvalidate?
Contactor Arm Disconnectarm disct 98 NY
Contactor Arm Load Monitorarm load 97 NY
Contactor Arm Modulearm mod 96 NY
Contactor Arm Opticalarm opt 95 NY
Contactor Close Buttonclose but 101 NY
Contactor Close Moduleclose mod 100 NY
Contactor Close Opticalclose opt 99 NY
Contactor Open Auto Disconnectopen aut 94 NY
Contactor Open Load Mon Highopen lmh 93 NY
Contactor Open Load Mon Lowopen lml 92 NY
Contactor Open Moduleopen mod 91 NY
Contactor Open Opticalopen opt 90 NY
Contactor Ready for Manual rcarm man 791 NN
Manual connectionmanconnect 695 NN
Relay control failedrelay err 778 NN
Relay Switched offrelay off 658 YN
Threshold exceededok lm 836 YN
  Externally generated
EventShortEvent IDTimespaninvalidate?
Breaker failureBf 744 NN

Event Category: Current Anomaly
(Current) (5)
  Internally generated
EventShortEvent IDTimespaninvalidate?
Back Flowbflow 132 NY
Consumption Above MaximumSpike 44 NY
Current No Voltagevt fail 773 NY
Current Over LimitI> 12 YY
Current Unbalancecbal 696 YN
Current Under ThresholdI< 80 YY
Leakleak 130 NY
No Load!load 832 YN
Overcurrent neutralCurrent= 37 YY
Phase sequence reversalph sq rev 697 YN
Pipe Burstburst 131 NY
Pipe Drydry 136 NY
Power factors exceededFactor+ 39 YY
Power factors fallen belowFactor- 38 YY
Power Unbalancepbal 821 YN
Reverse RunI<- 13 YY
  Externally generated
EventShortEvent IDTimespaninvalidate?
Consumption Above Max(Sw)Spike(S) 81 NY
Current Over Limit(Software)I>(S) 85 NY
Func disconnect energy limitFdel 739 NN
Func disconnect power limitFdpl 738 NN
Leak (S)Leak 138 NY
Pipe Burst (S)Burst 794 NY
Reverse Consumption (Software)I<0(S) 786 YN
Reverse Run (Software)I<-(S) 82 NY

Event Category: DIAGNOSTICS
(diag) (8)
  Internally generated
EventShortEvent IDTimespaninvalidate?
buffer limit reachedbuf limit 56 NY
End of IntervalEOI 124 NN
modem port overflowmpo 55 NY
Over-temperature thresholdovertemp 693 YY
RF Wireless Communicationrf err 818 NN
Under-temperature thresholdfreeze 713 YY
Unknown eventunknown 777 NN
  Externally generated
EventShortEvent IDTimespaninvalidate?
Alarm failedAf 728 NN
Alarm ON/OFFAOnOff 727 NN
Alarm output setAos 764 NN
Alarm requestAr 725 NN
Alarm sentAs 726 NN
External alarmEa 763 NN
External alarm 2Ea2 765 NN
External alarm 3Ea3 766 NN
External alarm 4Ea4 767 NN
Fraudfraud 741 YN
Hi Alarm, Instr (S)hi 672 YY
Hi Alarm Long, Instr (S)HI 676 YY
HiHi Alarm, Instr (S)hihi 673 YY
HiHi Alarm Long, Instr (S)HIHI 677 YY
Lo Alarm, Instr (S)lo 674 YY
Lo Alarm Long, Instr (S)LO 678 YY
LoLo Alarm, Instr (S)lolo 675 YY
LoLo Alarm Long, Instr (S)LOLO 679 YY
No dataNd 715 NN

Event Category: Power Loss & Return
(Power) (3)
  Internally generated
EventShortEvent IDTimespaninvalidate?
Battery FailureBattery! 16 YY
Battery voltage OKBattery^ 36 NY
Bypass Activated Relay 1Bypass R1 660 YN
Bypass Activated Relay 2Bypass R2 661 YN
Bypass Activated Relay 3Bypass R3 662 YN
Bypass Activated Relay 4Bypass R4 663 YN
Low BatteryBattery? 819 NN
Phase BreakPhase 2 YY
Power LossDown 10 YN
Power OnPower On 659 NN
Red Buttonred 708 YN
RTU Power LossRTU Down 11 YY
Start of measurementStart 665 NN
Yellow Buttonyellow 709 YN
  Externally generated
EventShortEvent IDTimespaninvalidate?
Generator PowerGenSet 667 YN
Lifeline Depletedll used up 683 YN
Long power interruption logLpil 724 NN
Power Loss(Software)Down(S) 86 YY

Event Category: Prepaid
(prepaid) (14)
  Internally generated
EventShortEvent IDTimespaninvalidate?
Account changeaccount 827 NN
Clear Tamperclr tamper 706 NN
Credit Lowclow 699 NN
Credit Tokentech token 704 NN
Key Changekey 705 NY
Overdraft activatedoverdr 826 NN
Prepay managementPP 822 NN
Pre/post-payment switchingpre-post 707 NN
Technical Tokentech token 703 NN
  Externally generated
EventShortEvent IDTimespaninvalidate?
Customer purchase requestCpr 749 NN
Incorrect credit codeIcc 745 NN
Prepay credit expiredPce 731 NN
Prepay EM credit activatedPEca 733 NN
Prepay EM credit expiredPEce 732 NN
Prepay token enter failedPtef 730 NN
Purchase Powercharge 671 NY
Token errorTe 772 NN
Token expiredTe 771 NN
Token usedTu 770 NN

Event Category: Quality of Supply
(QoS) (0)
  Internally generated
EventShortEvent IDTimespaninvalidate?
Active Power Over ThresholdP> 74 YY
Active Power Under ThresholdP< 75 YY
Apparent Power Over ThresholdS> 78 YY
Apparent Power Under ThresholdS< 79 YY
Control Equation ErrorAssert 650 NY
Daily 95% maximumdd MAX 40 YY
Daily 95% minimumdd MIN 41 YY
Daily phase maximumdd pMAX 42 YY
Daily phase minimumdd pMIN 43 YY
Disturbancefault 684 NN
End Of BillingEOB 89 NN
Frequency abnormalHz? 139 YY
Frequency Over ThresholdHz> 70 YY
Frequency Under ThresholdHz< 71 YY
Load Monitor High Triphi trip 88 NY
Load Monitor Low Triplo trip 87 NY
Maximum Demand ResetMD reset 698 NN
Neutral Line Missing!N 820 YY
Over Tot Harmonic Distortion Iharm I 669 YY
Over Tot Harmonic Distortion Uharm U 668 YY
Over Tot Harmonic Distortion Vharm V 670 YY
Passive TOU Programmedtouprog 689 NN
Phase Angle Over Thresholddeg> 72 YY
Phase Angle Under Thresholddeg< 73 YY
PIN Resetpin 690 NN
Power Factor Over Thresholdpf> 68 YY
Power Factor Under Thresholdpf< 69 YY
Power up/down resetpowreset 691 NN
Reactive energy reversal!reac 833 YN
Reactive Power Over ThresholdQ> 76 YY
Reactive Power Under ThresholdQ< 77 YY
Resetreset 692 NY
Reversed polarity!polarity 831 YY
TOU activatedtou 686 NN
Trigger State ChangeTrigger 651 NY
voltage connection problemV prob 58 YY
Voltage Over ThresholdV> 0 YY
Voltage Under ThresholdV< 1 YY
  Externally generated
EventShortEvent IDTimespaninvalidate?
Curtailment Exceeded>curt 782 YN
Curtailment Periodcurt 781 YN
Daily Consumption over limitdaily> 714 YY
Inverted current phaseIcLn 760 YN
Positive energy flow 3-phasePeft-p 721 NN
Positive energy flow phasePefL 722 NN
Unbalanced by currentUbI 761 YN
Unbalanced by voltageUbV 762 YN
Voltage Over Threshold(Softw)V>(S) 84 NY
Voltage Under Threshold(Softw)V<(S) 83 NY

Event Category: SETUP
(setup) (6)
  Internally generated
EventShortEvent IDTimespaninvalidate?
logoff userlogoff 50 NY
logon userlogon 49 NY
Parameter/s changedset 792 NY
Period too short period< 776 NY
user name changedusername 51 NY
  Externally generated
EventShortEvent IDTimespaninvalidate?
All codes enteredAce 748 NN
Energy registers resetEnrR 768 NN
Etech fullEf 751 NN
Intrusion resetIr 752 NN
Keypad lockedKl 746 NN
Memory Fullmem! 664 NN
Meter snapshotMs 750 NN
Overload disconnectionOD 769 NN
Private key changedPkc 742 NN
Setting with buttonsSwb 716 NN
Unreliable external controlUec 723 YN
Variable changed in SET modeVciSm 718 NN

Event Category: SYSTEM
(system) (7)
  Internally generated
EventShortEvent IDTimespaninvalidate?
efa clearedefa c 53 NY
efa latchedefa l 52 NY
External Alarm Triggeredext 127 YY
firmware activatedfirmw! 140 NY
firmware changedfirmw 54 NY
firmware ready for activationfirmw? 789 NN
initialized parameterinit parm 46 NY
Meter Errormet err 104 NY
Missing Addisional PSUmissing PS 774 NN
recovered extreced ext 48 NY
recovered parameterrp 45 NY
recovering extrec ext 47 NY
Watchdogwatchdog 126 YN

Event Category: Tampering
(Tamper) (4)
  Internally generated
EventShortEvent IDTimespaninvalidate?
Breaker overriddenoverride 701 NY
Bypassed( ) 835 NY
Chopper powerchop 830 NY
Cover Was Openedcover! 59 YY
Credit abnormalcred? 829 NY
Current by-passby-pass 779 YY
Decryption failuredecrypterr 694 NN
logon faileddenied 780 NN
Magnetic Tampermtamper 103 NY
Replay Attackreplayatt 834 NY
STS Tamper detectionTamper STS 700 NY
Terminal Cover Tampertamper 102 YY
Wire Cutcut 129 NY
  Externally generated
EventShortEvent IDTimespaninvalidate?
Intrusiveness - MCOI-MCO 719 NN
Intrusiveness - TCOI-TCO 720 NN
Seal changesealh 654 YN
Seal confirmsealc 653 YN
Seal discrepancyseald 655 YY
Seal installseali 652 YN
Tamper RTUrtamper 702 YY
Use while disconnectedoff use 793 YY

Event Category: Totals/Profile Audit
(Audit) (10)
  Externally generated
EventShortEvent IDTimespaninvalidate?
Consumption is less than Totalpro 62 YY
Consumption is more than Totalprof>tot 63 YY
Consumption > Limit (Sw)> 133 NY
E1 Consumption=0 Total<>0prof=0 61 YY
E2 Consumption=0 Total<>0prof=0 110 YY
F1 Consumption=0 Total<>0prof=0 111 YY
F2 Consumption=0 Total<>0prof=0 112 YY
F3 Consumption=0 Total<>0prof=0 113 YY
F4 Consumption=0 Total<>0prof=0 114 YN
pf < Limit (Sw)pf< 134 NY
Unexpected consumption!0 790 NY
Zero Consumption (Sw)zero 135 NY

Event Category: Totals/Profile Audit Error
(Audit err) (12)
  Externally generated
EventShortEvent IDTimespaninvalidate?
Cannot set Prof=Tot: many gapsinterp err 66 YY
E1 Cannot set Prof=Tot: manualaudit err 67 YY
E2 Cannot set Prof=Tot: manualaudit err 115 YY
F1 Cannot set Prof=Tot: manualaudit err 116 YY
F2 Cannot set Prof=Tot: manualaudit err 117 YY
F3 Cannot set Prof=Tot: manualaudit err 118 YY
F4 Cannot set Prof=Tot: manualaudit err 119 YN
TOU calendar wrong on metertou err 711 YY
TOU reg change with no profiletou err 710 YY
TOU reg in rt out with profiletou err 712 YY

Event Category: Totals/Profile Audit Warning
(Audit warn) (11)
  Externally generated
EventShortEvent IDTimespaninvalidate?
Excessive Total ReclocksRECLOCK 681 NY
Interp. Prof to match Totinterplt 65 YY
Recalc. Prev Tot to match Profrecalc tot 64 NY
Total Reclockedreclock 682 NY

Event Category: USER
(usr) (9)
  Internally generated
EventShortEvent IDTimespaninvalidate?
Is Not Calibrated!calib 824 NY
Passwordpassw 128 NY
user logged eventuser event 57 NY
  Externally generated
EventShortEvent IDTimespaninvalidate?
Additional Information (Sw)Info(S) 120 NN
Calibration Report (Sw)Tune(S) 122 NN
Manual Meter ReadHand Read 685 NN
Profile Editedprofile 680 YY
Savings Report (Sw)Saving(S) 121 NN
Site Visit (Sw)Visit(S) 123 NN

Event Category: Valve
(Valve) (16)
  Internally generated
EventShortEvent IDTimespaninvalidate?
Close Valve Failedclose err 817 NN
Open Valve Failedopen err 816 NN

Event IDs per Meter Type

DescriptionMeter typeClass IDproperty nameSupported EventIDs
ABB REF630ABB630FTP308ABB630ftp.prp 684
ABB REF630 (http)ABB630285ABB630.prp 16 28 25 34 6 27 91 100 684
Bluestar A2000 (RS485)BS_A2000174A2000.prp 59 10
Bluestar B2000 (RS485)BS_B2000202B2000.prp 10
CLOU DLMS meterCLOUDLMS350CLOUDLMS.prp 777 10 740 33 8 34 16 686 787 788 20 28 25 789 54 689 60 698 792 705 26 5 30 59 779 102 103 780 13 790 791 658 12 778 1 0 69
Conlog DLMS meterCONLOGDLMS396genericdlms.prp 0 1 2 8 13 25 26 30 33 35 36 54 58 59 90 91 99 100 102 103 127 137 140 664 670 680 686 689 694 695 697 700 705 706 736 740 744 770 780 787 788 789 790 791 792 819 820 834 835 836
Elster A1140Elster A1140107elsterA1140.prp 82 10 5 8 6 107 2 12 13 14 4 54 54 1 0 3 16 44 68 102 105 106
Elster A1160Elster A1160215elsterA1140.prp 82 10 5 8 6 107 2 12 13 14 4 54 54 1 0 3 16 44 68 102 105 106
Elster A140Elster A140119elster.prp 82 10 5 8 6 107 2 12 13 14 4 54 54 1 0 3 16 44 68 102 105 106
Elster A1700Elster A1700106elster.prp 82 10 5 8 6 107 2 12 13 14 4 54 54 1 0 3 16 44 68 102 105 106
Elster A220Elster A220127elsA220.prp 28 25 9 5 8 10 6 60 59 14
Elster AS1440Elster AS1440162elsA220.prp 28 25 9 5 8 10 6 60 59 14
Elster AS220Elster AS220252elsterAS3000.prp 9 8 5 60 25 32 10 28 59 6
Elster AS230Elster AS230154elsAS230.prp 82 10 5 8 6 107 2 12 13 14 4 54 87 88 90 91 92 93 94 95 96 97 98 99 100 101 0 1 6 51 10 102 59 103 13 10 60 89 54 104 16 105 106
Elster AS3000Elster AS3000253elsterAS3000.prp 9 8 5 60 25 32 10 28 59 6
Elster AS3500Elster AS3500270elsterAS3000.prp 9 8 5 60 25 32 10 28 59 6
EMHEMH398emh.prp 9 8 5 60 25 32 10 28 59 6
Generic BACnet Elect MeterGeneric BACnet200bacnet.prp 17
Hexing HXF300 DLMSHexingDLMS300263HexingDLMS300.prp 0 1 2 5 6 8 10 12 13 25 26 30 33 35 36 38 46 57 59 60 74 80 89 91 100 102 103 104 128 137 139 140 658 664 669 670 671 686 689 692 696 697 698 699 705 740 756 762 768 778 779 780 787 788 789 793 819 820 821 822 823 824 825 826 827 829 830 831 832 833
Hexing Single Phase DLMS STSHexingDLMS251HexingDLMS.prp 57 33 8 671 59 102 91 100 10 1 74 0 703 704
Hexing Three Phase DLMS STSHexingDLMS310261HexingDLMS310.prp 57 33 8 671 59 102 91 100 10 1 74 0 703 704
Holley MTR3000/3500HolleyMTR3000335HolleyMTR3000.prp 57 10 59 699 705 706 19 707 704 703 658 660 13 8 33 4
Honeywell HS100HS100336hs100.prp 777 740 33 8 34 16 686 787 788 20 28 25 789 54 689 60 698 718 705 26 5 30 59 779 103 780 13 658 778 10 1 0 74
Inhemeter Single phase DLMS STSInheDLMS302InheDLMS.prp 57 10 59 699 705 706 19 707 704 703 658 660 13 8 33 4
Inhemeter Single phase DL/T645 STS via RS-485InheDLT645312INHE2.prp 57 10 59 658 4
Inhemeter Three phase DLMS STSInheDLMS3333InheDLMS.prp 57 10 59 699 705 706 19 707 704 703 658 660 13 8 33 4
IskraeMECO MT172ISKRAME172342iskra.prp 704 16 8 5 60 684 89 46 103 104 106 105 128 2 10 680 26 13 31 28 59 14 58 0 1 126 697 707 715 716 717 718 719 720 721 722 723 724 725 726 727 728 729 730 731 732 733 734 735 736 737 740 741 742 743 744 745 746 747 748 749 750 751 752 753 754 755 756 757 758 759 760 761 762 763 764 765 766 767 768 769 770 771 772
IskraeMECO MT174ISKRAMT174318iskra.prp 704 16 8 5 60 684 89 46 103 104 106 105 128 2 10 680 26 13 31 28 59 14 58 0 1 126 697 707 715 716 717 718 719 720 721 722 723 724 725 726 727 728 729 730 731 732 733 734 735 736 737 740 741 742 743 744 745 746 747 748 749 750 751 752 753 754 755 756 757 758 759 760 761 762 763 764 765 766 767 768 769 770 771 772
IskraeMECO MT830/1ISKRA241iskra.prp 704 16 8 5 60 684 89 46 103 104 106 105 128 2 10 680 26 13 31 28 59 14 58 0 1 126 697 707 715 716 717 718 719 720 721 722 723 724 725 726 727 728 729 730 731 732 733 734 735 736 737 740 741 742 743 744 745 746 747 748 749 750 751 752 753 754 755 756 757 758 759 760 761 762 763 764 765 766 767 768 769 770 771 772
IskraeMECO MT880ISKRAMT880332iskra.prp 704 16 8 5 60 684 89 46 103 104 106 105 128 2 10 680 26 13 31 28 59 14 58 0 1 126 697 707 715 716 717 718 719 720 721 722 723 724 725 726 727 728 729 730 731 732 733 734 735 736 737 740 741 742 743 744 745 746 747 748 749 750 751 752 753 754 755 756 757 758 759 760 761 762 763 764 765 766 767 768 769 770 771 772
Itron ACE6000ACE6000173ACE6000.prp 124 89 5 125 9 4 46 3 126 34 27 20 26 59 37 0 12 34 127 13 2 1 0 44 16 12 103 60 19 6 14 8 71 10 7 4 25 128
Kamstrup Head end MeterKamstrup214kamstrupmeter.prp 10 102 103 57 46 130 136 13 131
Kamstrup Meter (KMP)KMP290kamstrupKMP.prp 28 25 9 5 8 10 6 60 59 14
Kamstrup Tariff Meter (KMP)KMP Tariff377kamstrupKMP.prp 28 25 9 5 8 10 6 60 59 14
Laison Meter (LORA)LaisonLORA360LLORA.prp 59 692 103 816 817 131 13 819 818
Landis & Gyr (DLMS)LGZDLMS319lgzdlms.prp 764 104 16 776 740 692 8 10 60 5 33 773 17 36 3 9 18 1 0 12 37 38 39 19 774 697 34 20 35 22 21 23 24 25 26 27 28 29 30 775 31 32 718 59 103
Linyang MeterLinyang Meter276Linyang.prp 764 698 89 10 33 8 59 20 102 658 1 0 2 58 770 704
LogicLogger GenesesLogicLogger Genesis298ll.prp 764 698 89 10 33 8 59 20 102 658 1 0 2 58 770 704
LONGiLONGi339Longi.prp 764 698 89 10 33 8 59 20 102 658 58 1 0 2 770 704
MetComMetCom376metcom.prp 9 8 5 60 25 32 10 28 59 6
MOL 0643MOL0643397mol0643.prp 0 12 74 76 1
Orbis Contax DBusOrbis Contax DBus271orbis.prp 0 12 74 76 1
Pulse Meter (Totals)Pulse Meter (Totals)108waveflow.prp 124 16 59 38 39 25 13 129 130 131 132
RT Real LogRT Real Log286UtilitySystems2.prp 660 102 4 100 22 131
Sanxing MetersSANXING283Sanxing.prp 10 33 8 34 16 36 686 30 664 126 25 4 54 689 698 699 6 5 60 690 691 692 30 693 694 59 103 59 20 12 59 671 695 91 100 90 93 101 1 0 2 660 80 696 13 69 13 77 76 697 700 18 701
Schneider PM3255Schneider PM3255231schneider.prp 12 80 0 1 2 74 76 78 69 38 74 78 668 75 669 670 74 57 10
Schneider PM5560Schneider PM5560390schneider.prp 12 80 0 1 2 74 76 78 69 38 74 78 668 75 669 670 74 57 10
Secure Apex DLMS meterAPEXDLMS351APEXDLMS.prp 777 10
SEL734/5 (Telnet)SEL734204SEL734.prp 1 0 10 57 650 651
SEL751A (Telnet)SEL751204SEL751.prp 1 0 10 57 650 651
Sensus iPerl Water MeterSensus iPerl Water258SensusiPerl.prp 16 130 103 104 132 131 136 650
Sensus Scout Water MeterSensus Scout Water198SensusScout.prp 131 130 129 104 16 132 21
Siemens IM100IM100307siemenswasionIM300.prp 10 126 9 14 8 665
Siemens IM300IM300216siemenswasionIM300.prp 10 126 9 14 8 665
SL7000SL7000140SL7000.prp 124 89 5 125 9 4 46 3 126 34 27 20 26 59 37 0 12 34 127 13 2 1 0 44 16 12 103 60 19 6 14 8 71 10 7 4 25 128
Utility Systems WMD via RTS Real LogUtilitySystems2287UtilitySystems2.prp 660 102 4 100 22 131
Utility Systems WMD via UtiliHubUtilitySystems280UtilitySystems.prp 660 102 4 100 22 131 103 683
Vixnet ManziVixnet Manzi246vixnet.prp 102
Wasion/Netvendor STS meterWASION234WASION.prp 10 671 59 102 18
Wasion STS DLMSWasion STS DLMS341siemenswasionIM300.prp 10 126 9 14 8 665
Water (Totals)Water (Totals)108waveflow.prp 124 16 59 38 39 25 13 129 130 131 132
Wavenis ModuleWavenis143waveflow.prp 124 16 59 38 39 25 13 129 130 131 132